您好,欢迎来到中国测试科技资讯平台!

首页> 《中国测试》期刊 >本期导读>基于小波能量熵的电磁式电压互感器绕组故障检测

基于小波能量熵的电磁式电压互感器绕组故障检测

385    2024-07-25

¥0.50

全文售价

作者:古亮1,2, 蔡瑜1, 陈新岗1,2, 胡晓倩1,2, 刘帮藩1, 冯波1,2

作者单位:1. 重庆理工大学电气与电子工程学院,重庆 400054;
2. 重庆市能源互联网工程技术研究中心,重庆 400054


关键词:电磁式电压互感器;绕组层间绝缘;冲击响应;小波能量熵


摘要:

电磁式电压互感器高压绕组层数多,绕组端部电场变化剧烈,长期运行极易导致绕组层间绝缘故障。为进一步提高绕组层间故障诊断的可靠性,提出一种基于冲击响应电压小波能量熵的电磁式电压互感器绕组绝缘检测方法。该方法采用高压脉冲波对正常电压互感器和故障电压互感器原边分别进行冲击实验,利用sym4小波对高压绕组冲击响应电压信号进行离散小波分解和重构以消除噪声信号的干扰,并用重构的信号计算小波能量熵,作为绕组层间故障诊断的特征参量。实验结果表明正常绕组与放电故障和短路故障绕组的小波能量熵区分度为86.5%和28.3%,可以有效判别绕组层间绝缘状态,根据故障绕组的小波能量熵值大小可以较好地区分故障类型。


Interlayer insulation fault detection of electromagnetic voltage transformer winding based on wavelet energy entropy
GU Liang1,2, CAI Yu1, CHEN Xin’gang1,2, HU Xiaoqian1,2, LIU Bangfan1, FENG Bo1,2
1. School of Electrical and Electronic Engineering, Chongqing University of Technology, Chongqing 400054, China;
2. Chongqing Energy Internet Engineering Technology Research Center, Chongqing 400054, China
Abstract: There are many layers of high voltage winding of electromagnetic voltage transformer, and the electric field at the end of winding changes dramatically. Long-term operation is easy to cause the insulation fault between winding layers. In order to further improve the reliability of inter-layer winding fault diagnosis, a electromagnetic voltage transformer winding inter-layer insulation detection method based on wavelet energy entropy of impulse response voltage is proposed in this paper. The method adopt high-voltage pulse wave to carry out the impulse experiment on the primary side of the normal voltage transformer and the fault voltage transformer respectively. Then sym4 wavelet is used to decompose and reconstruct the impulse response voltage signal of the high-voltage winding to eliminate the interference of the noise signal. And the reconstructed signal is used to calculate the wavelet energy entropy, which is used as the characteristic parameter of the fault diagnosis between the winding layers. The experimental results show that the wavelet energy entropy differentiation between normal winding and discharge fault winding is 86.5%, and that between normal winding and short-circuit winding fault is 28.3%, which can effectively distinguish the insulation state between windings. The fault type can be well distinguished according to the wavelet energy entropy of the fault winding.
Keywords: electromagnetic voltage transformer;interlayer insulation of winding;impulse response;wavelet energy entropy
2024, 50(7):99-106  收稿日期: 2022-07-21;收到修改稿日期: 2022-09-18
基金项目: 重庆市教育委员会科学技术研究项目(KJQN202101147)
作者简介: 古亮(1976-),男,重庆市人,副教授,博士,主要从事电气设备状态监测和故障检测。
参考文献
[1] 姜春阳, 刘俭, 王雪, 等. 电磁式电压互感器谐波误差测量方法研究[J]. 中国测试, 2021, 47(3): 163-168.
JIANG C Y, LIU J, WANG X, et al. Research on test method of harmonic measurement error of inductive voltage transformer[J]. China Measurement & Test, 2021, 47(3): 163-168.
[2] 赵鹏, 马克琪, 李红斌, 等. 计及一次电压波动的电压互感器误差状态在线评估方法[J]. 高电压技术, 2022, 352(3): 1042-1051.
ZHAO P, MA K Q, LI H B, et al. On-line error evaluation method of instrument voltage transformers considering primary voltage fluctuations[J]. High Voltage Engineering, 2022, 352(3): 1042-1051.
[3] 刘俭, 姜春阳, 殷小东, 等. 谐波电压互感器宽频特性试验研究[J]. 中国测试, 2021, 47(8): 130-136.
LIU J, JIANG C Y, YIN X D, et al. Study on frequency characteristics of harmonic voltage transformer[J]. China Measurement & Test, 2021, 47(8): 130-136.
[4] 何帅, 赵雨濛, 邰晨凡, 等. 一起半绝缘电压互感器故障原因分析及处理措施[J]. 宁夏电力, 2020(3): 67-70.
HE S, ZHAO Y M, TAI C F, et al. Analysis and treatment of a fault of semi-insulated voltage transformer[J]. Ningxia Electric Power, 2020(3): 67-70.
[5] 李良书, 韩彦华, 李晋, 等. 电容式电压互感器典型故障案例分析[J]. 变压器, 2020, 57(9): 72-76.
LI L S, HAN Y S, LI J, et al. Typical fault case analysis of capacitor voltage transformer[J]. Transformer, 2020, 57(9): 72-76.
[6] 刘亮, 蒋鑫, 师普辛, 等. 发电机出口电压互感器绝缘缺陷检测方法[J]. 电网技术, 2016, 40(12): 3966-3972.
LIU L, JIANG X, SHI P X, et al. A Novel methodology for insulation defect detection in voltage transformer in generator circuit[J]. Power System Technology, 2016, 40(12): 3966-3972.
[7] HEWITT D A, HU R G, WANG J B. Early detection of turn-to-turn winding faults using a PWM ripple current based method[C]// IEEE The 10th International Conference on Power Electronics, 2020.
[8] 吴振宇, 周利军, 周祥宇, 等. 基于振荡波的变压器绕组故障诊断方法研究[J]. 中国电机工程学报, 2020, 40(1): 348-357+401.
WU Z Y, ZHOU L J, ZHOU X Y, et al. Research on fault diagnosis method of transformer winding based on oscillatory wave[J]. Proceedings of the CSEE, 2020, 40(1): 348-357+401.
[9] 普子恒, 张宇娇, 方春华, 等. 雷电冲击下换流变压器绕组故障模拟与诊断方法[J]. 中国电机工程学报, 2017, 37(5): 1552-1560.
PU Z H, ZHANG Y J, FANG C H, et al. Fault simulations and diagnosis methods of converter transformer windings under lightning impulse voltages[J]. Proceedings of the CSEE, 2017, 37(5): 1552-1560.
[10] 尹璇, 邓祥力, 游及第. 基于MODWT的变压器绕组轻微故障检测及分类研究[J]. 电测与仪表, 2019, 56(14): 103-109.
YIN X, DENG X L, YOU J D, et al. Study on the detection and classification transformer winding slight fault based on MODWT[J]. Electrical Measurement & Instrumentation, 2019, 56(14): 103-109.
[11] FAIFER M, LAURANO C, OTTOBOBI R, et al. Nonlinear behavioral modeling of voltage transformers in the frequency domain: comparing different approaches[J]. IEEE Transactions on Instrumentation and Measurement, 2020, 69(10): 8137-8145.
[12] 郭成, 叶壮, 孟贤, 等. 电容式电压互感器电路参数对暂态误差影响研究[J]. 高压电器, 2021, 57(12): 131-139.
GUO C, YE Z, MENG X, et al. Study on influence of circuit parameters of capacitor voltage transformer on transient error[J]. High Voltage Apparatus, 2021, 57(12): 131-139.
[13] 张立石, 梁得亮, 刘桦, 等. 基于小波变换与逻辑斯蒂回归的混合式配电变压器故障辨识[J]. 电工技术学报, 2021, 36(S2): 467-476.
ZHANG L S, LIANG D L, LIU H, et al. Fault identification of hybrid distribution transformer based on wavelet transform and logistic regression[J]. Transactions of China Electrotechnical Society, 2021, 36(S2): 467-476.
[14] 范国栋,李博涵.基于机器学习的工业机械设备故障预测方法[J].自动化与信息工程,2023,44(4):13-18.
FAN G D, LI B H. Fault prediction method of industrial machinery equipment based on machine learning[J]. Automation & Information Engineering, 2023,44(4):13-18.
[15] 刘红文, 王科, 林桐, 等. 基于离散小波的变压器绕组振荡波故障检测方法[J]. 变压器, 2020, 57(1): 58-62.
LIU H W, WANG K, LIN T, et al. Detection method of transformer winding oscillation wave fault based on discrete wavelet transform[J]. Transformer, 2020, 57(1): 58-62.
[16] DENG Y J, LIN S, FU L, et al. New criterion of converter transformer differential protection based on wavelet energy entropy[J]. IEEE Transactions on Power Delivery, 2019, 34(3): 980-990.